name='google-site-verification'/> Marine Engineering 360: Generator
Showing posts with label Generator. Show all posts
Showing posts with label Generator. Show all posts

Thursday, April 28, 2016

Generator Synchronization Procedure



Generator synchronization
is the process of the closing circuit breaker after matching the generator frequency, phase angle & voltage magnitude with grid voltage frequency, phase angle & magnitude respectively. Simply it is used to close the circuit breaker after synchronization check.


Conditions:
In order to synchronize a generator to the grid, four conditions must be met:
  1. Phase Sequence
  2. Voltage Magnitude
  3. Frequency
  4. Phase angle

Synchronizing procedure
  1. Once the engine starts running properly, synchronization is carried out.
  2. In the Engine control room, Check the pressure gauges.
  3. On the generator control panel, check if all the ground lights are working properly with adequate brightness.
  4. Also check the synchronizing relays for open position. Bring the running or the lead generator to the desired optimum parameters: 480 volts and 60 hertz.
  5. Bring the generator that is to be synchronized(in-coming) to the desired parameters. Now turn on the synchronizing relay and keep a close look at the needle.
  6. The needle in the synchroscope will move at a varying speed initially. Adjust the speed of the generator by obtaining a steady slow motion of the needle in the clock wise direction.
  7. Once the needle is moving at a steady speed, depress the breaker close button when the needle has traveled three-fourth of its way. Energize the breakers when the needle reaches a position similar to the 11' o clock position of a clock.
  8. After doing this, check the parameters of the on-coming generator. They should be same as those of the leading generator. i.e 480 Volts and 60 hertz
After synchronizing
  1. After the main job of synchronizing, the following steps are to be carried out.
  2. Change the governor control to the off-going generator.
  3. Now the load shown in the gauges by this generator should be removed off the system as soon as possible before it starts acting as load(reverse power). This can be done by quickly pulling the trip breaker as soon as the generator goes off-line.
  4. Once the generator is offline, stop the engine using a toggle switch.
  5. After turning off the engine, turn on the engine block heater.
  6. At the end, take a proper look at the control panel gauges for adequate pressure and even distribution of load.

It must also be noted that load distribution can be adjusted by varying the fuel supply to the generator via its governor but for current sharing to be equal you would need to vary the excitation current which changes the power factor of the generator.

----------------------------------------------------------------------------------------

Monday, April 25, 2016

Maintenance Of Emergency Generators On Ship

Emergency Generator like any other normal generator on ship is required for the purpose of production of power (Electricity). But as name suggests, it is to be used in case of the emergency like Black Outs, getting ship to live after dead condition. Since the entire generator on a ship lies in the engine room, there has to be a source of supply that is outside this machinery space. Reason, well engine room is highly prone to fires and other factors, and thus there is a need of generator which is outside this space.

Otherwise:
  1. It is a small separate generator which supplies the electric power for emergency load in the event of main power supply failure. 
  2. It is located outside the main and auxiliary machinery space and not forward of the collusion bulkhead. 
  3. It has own switchboard near vicinity. 
  4. It is provided with independent means of automatically starting (by air or battery) to ensure immediate run up following a main power failure and repeated starts of at least 3 times, and further attempt can be made within the 30 minutes.
  5. Adequate and independent supply of fuel with a flash point of not less than 43 °C
  6. Must be able to be started in cold condition up to zero (0 °C)
  7. For cold weather, JCW system must be treated with anti-freeze agent, and heating arrangement provided.

Rules and Regulations for Emergency Power Sources

  • Emergency generator shall be automatically started and connected within 45 sec
  • Emergency power source, Emergency generator must be sufficient to operate certain essential services at least for the period of 18 hours .
  • 1) Emergency lightening (at alley way, stairways and exits, muster and embarkation stations, machinery space, control room, main and emergency switchboard, firemen’s outfits storage positions, steering gear room)2) Fire detecting and alarming system
    3) Internal communication equipment
    4) Daylight signaling lamp and ship’s whistle
    5) Navigation equipment
    6) Navigation lights
    7) Radio installations, (VHF, MF, MF/HF)
    8) One of the fire pumps, emergency bilge pump


Procedure for starting emergency generator when black out occurs ?

  1. Normally emergency generator cut in automatically when main power fails
  2. Starting is initiated by start up relay
  3. Falling of frequency or voltage of Main power, cause the start up relay to operate generator starting equipment
  4. If this system fails, after switching the MODE selector to Manual (Local) position, generator can be started manually by means of Back up starting equipment within 30 minutes of transitional emergency power battery lighting.

Maintenance:

Following are some important maintenance jobs that need to be carried out in emergency generators on ships:

1. Change of Engine Sump Oil: It is important to check the oil level in the sump regularly. Since the emergency generator is kept on auto mode, which ensures the generator starts and comes on load automatically, it is necessary that before starting the engine for operation, oil level is checked on regularly basis. The condition of the oil will be known during this period and if the oil is having carbon or soot particles, change of complete oil system needs to be done. The running hours for changing of engine oil depends on the manufacturer, the engine make and the oil grade in use. Normally it is done between 250-500 hrs.

2. Clean Air Cleaner: The combustion air for the engine is passed through an air filter, which can be of following types:

1. oil bath air cleaner

2. dry type air cleaner (cartridge or dust collector).

It is important to clean the air filter at correct intervals of time as delay will lead to clogging and less air going in the engine. This will reduce the efficiency of the engine and increase the thermal parameters. When using dry cartridge, ensure to replace them at intervals stated by the maker. Normal replacement schedule is one year or after 5-7 cleanings.

3. Check Water Separator: Some emergency generators are provided with water separator to prevent mixing of water with fuel. Check the level of water and make sure it is below the marked level and regularly drained off. This is to be done to avoid rust and corrosion of fuel line devices and to avoid incomplete combustion.

4. Check Electrolyte in the Battery: A battery is used in one of the starting methods of the emergency generator. The electrolyte level in the battery must be checked at regular intervals either by inserting a level stick or by checking the water level in the level tester cap (if provided). Use distilled water to make up for the low level.

5. Check Alarms and Shutdowns:
All the safety devices and alarms fitted in the emergency generator must be checked and tested regularly. Generator with V-belts have additional alarm which will be sounded in the event of belt failure and operated by idler pulley.

6. Check V belt Tension: When V belt is fitted, inspect the same for cracks and damages. Renew the belt if damage/ cracking appearance is more. To check the belt tension, press the belt by thumb in midway of the pulleys and check the inward deflection in mm. It should not be more than 10-15 mm depending upon the make of the generator.

7. Clean Oil Filter Cartridge: The emergency generator is provided with various oil filters such as by pass filter, centrifuge filter, lube oil filter, fuel feed pump filter etc. These filters need to be cleaned or renewal of filter cartridge is to be carried out as per the maker’s instruction or oil condition.

8. Check Valve Clearance: The tappet clearance of the inlet and exhaust valve should be checked at running hours stated in the maintenance section of the generator’s manual. Also ensure the engine is cold before taking the tappet clearance.

Loss of emergency generators at times when they are needed the most can lead to unfortunate and disastrous incidents. Followed a proper planned maintenance system along with thorough regular checks is the key to ensure smooth running of emergency generators on board ships.

--------------------------------------------------------------------

Reference: